Technical specifications of mobile gas station container type

          1. CONTAINER

Metallic structure and thermal protection panels

  • Sandwich panels 40mm
  • Aluminum door with closing system at the technical compartment
  • Aluminum door with closing system at the withdrawal pump compartment
  • Aluminum door with closing system at the reservoir compartment
  • Polycarbonate and solar protection blind
  • Metal ladder to reach the upper part of the container
          2. Double walls Reservoir with 2 compartments

Gasoline reservoir

  • Aperture with DN 600 cover
  • Technological filling pipeline 2”
  • Suction pipeline 2” provided with closing tap and anti-siphon valve
  • Automatic measuring of the fuel’s level aperture and cover
  • Hand measuring of the fuel’s level aperture and cover
  • Level probe with water/fuel/density kit
  • Sampling refill/sample aperture with cover
  • Gasoline vapors recovery aperture VRS
  • Leakage recovery aperture
  • Air aperture reservoire 2” provided with flame stopper and pressure valve
  • Leakage in the shell of the tank detection aperture

Diesel reservoir

  • Aperture with DN 600 cover
  • Technological filling pipeline 2”
  • Suction pipeline 2” provided with closing tap and anti-siphon valve
  • Automatic measuring of the fuel’s level aperture and cover
  • Hand measuring of the fuel’s level aperture and cover
  • Level probe with water/fuel/density kit
  • Sampling refill/sample aperture with cover
  • Leakage recovery aperture
  • Air aperture reservoire 2” provided with flame stopper
  • Leakage in the shell of the tank detection aperture
  • The tanks are metrological calibrated with certificates given by Direction of Legal Metrology
          3. Withdrawal pump compartment
  • DIESEL FUEL pump with 2” valve and 3” fast connection for charging
  • GASOLINE pump with 2” valve and 3” fast connection for charging
  • 2” pipeline with vapors of gasoline recovery valve
  • ON/OFF switch (withdrawal pump)
  • Antiex lamp and switch
  • Gas and termic detection sensor
  • Leeakage from gasoline/diesel fuel pumps revovery tray
         4. Technical compartment
  • Electric panel
  • Electric fuse
  • Antiex avary switch, type “Emergency”, provided with release key
  • Gas leaking alarm clock
  • Console with display (fuel level in reservoir) and level probes
  • Central leakage detection
  • Lightning lamp + switch
  • Automatic fire extinguishing system and guide with fire extinguisher type P50 with dust, 50 kg and electrovalve
  • Manual switch for fire extinguishing
  • Fire extinguishing 1” piping connected to the P50 extinguisher
          4. Gasoline/diesel Fuel distribution pump

2 products: gasoline and deles fuel

  • Flow: 40 l/min gasoline, 70-80 l/min diesel fuel
  • Elaflex hose 3,3 ml and ZVA rod
  • Three phase 400 V engine
  • Calculator
  • Flow meter with four rods
  • Display
  • Communication protocol
  • Electromechanical totalizer
  • MID certificate, ATEX certificate
  • Access key to displays and engine distribution
          5. Graduated 3 cm rule, metrological approved
          6. Surveillance system, outside and inside